How wiring inside a switchboard or distribution panel is first organized decides whether later inspection and added circuits are easy or painful. Only a few parts are involved: cable ties to bundle, tie mounts to hold bundles to the panel, cable clamps for one or two wires, and marker cable ties that act as labels. Based on the Allpum specification tables, here is where each part goes and how they fit together.
What each part does
| Part | Role | Allpum product |
|---|---|---|
| Cable tie | Bundles wires running the same way | AP series, 100–780 mm |
| Tie mount (screw) | Anchors bundles to a panel or frame with a screw | APTM-2S, 3S |
| Adhesive mount | Sticks on where drilling is impractical | APTM-19, 25 |
| Cable clamp | Holds single wires or small bundles with a screw | APCC0, 9 sizes, 2.8–14.0 mm inner Ø |
| Marker cable tie | Labels a circuit while fastening | APMK-1M, 2M |

Match the mount to the tie width
The first thing to check when choosing a mount is the cable tie width it accepts. A tie that is too wide will not pass through; one that is too narrow lets the bundle slide on the mount. Here is how common AP series sizes match the mounts.
| Cable tie (width) | APTM-2S | APTM-3S | APTM-19 | APTM-25 |
|---|---|---|---|---|
| AP100, APMK (2.5 mm) | ○ | — | ○ | ○ |
| AP140 (3.6 mm) | ○ | — | ○ | ○ |
| AP200, AP300 (4.8 mm) | ○ | ○ | — | ○ |
| AP270 (6.0 mm) | — | ○ | — | — |
| AP370 (7.6 mm) | — | ○ | — | — |

Step by step
- 1. Group by circuit First separate wires by breaker and by direction. Mixing circuits in one bundle makes it hard to work on just one later.
- 2. Place the mounts Set mounts at regular intervals along the bundle route. Use screw mounts where you can drill the panel, adhesive mounts where you cannot.
- 3. Bundle Thread a tie through the mount, wrap the bundle and pull. Tighten only until the jackets are not crushed, and cut the tail flush with the head so no sharp end is left.
- 4. Clamps for single runs Use cable clamps for wires that branch off to terminals or run alone. Pick the inner diameter that fits the wire’s outer diameter.
- 5. Label Add a marker cable tie near the bundle or terminal and write the circuit name on it.
Choosing a cable clamp inner diameter
| Item | Inner Ø A | Item | Inner Ø A |
|---|---|---|---|
| APCC0-2N | 2.8mm | APCC0-7N | 10.7mm |
| APCC0-3N | 4.6mm | APCC0-8N | 11.9mm |
| APCC0-4N | 5.6mm | APCC0-9N | 13.5mm |
| APCC0-5N | 7.4mm | APCC0-10N | 14.0mm |
| APCC0-6N | 10.0mm |
If the clamp is much larger than the wire, the wire moves inside the loop; if it is too small, it presses into the jacket. Measure the wire’s outer diameter and choose an inner diameter slightly larger.
Points to watch
- Leave slack before terminals Pulling wires taut into a terminal strains the connection and leaves no length for reconnecting later. Leave some slack between the last mount and the terminal.
- Wiring across doors and hinges Wires to parts on the door move each time it opens, so do not tie the bending section too tightly.
- Where flame retardancy is required If the installation calls for flame-retardant materials, see the flame-retardant cable tie (APF) data. APF’s UL94 V-0 is a resin rating, not a certification of the finished tie.
- Operating temperature AP series and marker cable ties are rated -40 to 85 °C. For hotter spots, consider heat-resistant cable ties (APH).
How to choose between mount types, how to apply adhesive mounts and how to fasten cable ties are covered in the posts below. Check sizes and packing quantities in each product’s specification table.